Before Placing the Control and
the Recloser into Service

Prior to placing the control and recloser into service, the
following installation procedures must be properly com-
pleted and verified:

1. Control properly mounted for the installation.

2. Recloser installed according to all locally approved

standards and practices.

3. Control and recloser properly grounded in accordance

with guidelines in this manual.

4. AC power connected to the control. (AC power LED

indicator is illuminated.)

5. Control battery connected and tested for proper

operation.

6. All control programming entered and verified by

appropriate personnel.

7. Control clock set to the correct time.

8. Customer connections for remote and supervisory

operation checked and completed in accordance with
proper shielding and surge protection.

9. Control cable properly connected and supported.

Kyle Form 5, Form 5 UDP, Form 5 DC NOVA Recloser Control Installation and Operation Instructions

42

CAUTION: Equipment misoperation. Do not

connect this control to an energized recloser

until all control settings have been properly pro-
grammed and verified. Refer to the programming
information for this control. Failure to comply can
result in control and recloser misoperation, equip-
ment damage and personal injury.

G110.3

!

WARNING: Hazardous voltage. Recloser and

control must be solidly grounded. Follow all

locally approved procedures and safety practices when
grounding this equipment. Improper grounding can
result in contact with high voltage, which will cause
death or severe personal injury.

G115.1

!