SAFETY

FOR LIFE

3

6

4

T3

Y

H

X

Z

VOLTAGE RATING OF
RECLOSER CLOSING
SOLENOID COIL

SENSING CTs (3)

CLOSING
SOLENOID
CONTACTOR

ROTARY
SOLENOID

MAIN
CONTACTS (S)

G

K

A

B

E F

TO
240 OR
480 VAC
SOURCE

TO
240 VAC
SOURCE

CLOSING
SOLENOID
COIL

TRIP
SOLENOID

CONTROL
CABLE RECEPTACLE

W

ELECTRONIC
CONTROL

TO
AMMETER AND RELAY TO
OPERATE CYCLE COUNTER
OR OTHER TIMING DEVICE

120 VAC

VARIABLE
AUTOTRANSFORMER
240 VAC
20 AMPS

T2

1

2

5

J

Figure 45.
Suggested test circuit for “shop-testing” solenoid-closing reclosers.

5

6

3

4

1

2

C

B

A

BYPASS SWITCHES

(CLOSED)

SOURCE SIDE
DISCONNECT SWITCHES
(CLOSED)

LOAD SIDE
DISCONNECT SWITCHES
(OPEN)

CLOSING

COIL

LOAD

SOURCE

SOURCE

LOAD

Figure 44.
Closing source-side switches of a bypassed “on-line” recloser provides closing solenoid power for automatic
operation during testing.