beautypg.com

Cooper Lighting S280-79-10 User Manual

Page 35

background image

Installation of a Form 5 control with a local supply voltage
transformer must include the following:

• Protection of the recloser bushings and the supplying

transformer with lightning arresters.

• Grounding of the recloser head and tank.

• Grounding of the transformer tank.

• Grounding of the control cabinet.

• Grounding of the SCADA equipment.

4-Wire Multi-Grounded Systems

3-Wire Ungrounded and Impedance Grounded Systems

The use of a grounding mat may be required depending
upon the local safety regulations defining the permissible
step and touch potential levels. Consult local regulations
for proper grounding procedures.

S280-79-10

35

!

SAFETY

FOR LIFE

Surge
Arrester

Recloser
Head Ground

Surge

Arrester

Transformer

Surge

Arrester

Arrester Ground

Recloser

Pole

Supply

Voltage

Pole

Ground

Form 5 LS
Control

Customer Ground Connection
At External Lug

NEU

AC

GND

NEU

AC

Input
Terminal
Block

Control

Cable

AC

NEUTRAL

Form 5 LS Control

Supply Voltage

Transformer

ELECTRICAL CONNECTIONS

Line to Neutral connected transformer

Form 5 LS Control

AC

NEUTRAL

Input Terminal
Block

Supply Voltage

Transformer

ELECTRICAL CONNECTIONS

Line to Line connected transformer

Line
to
Line
Voltage

External
Ground Lug

Input Terminal

Block

External
Ground Lug

Figure 29.
Recommended grounding method for the Form 5 Control installed on 4-wire multi-grounded, 3-wire
ungrounded, or impedance-grounded systems with local supply voltage transformer.

IMPORTANT: In pole-mounted applications, a
ground connection must be made between the
recloser, transformer, recloser control, and SCADA
equipment for proper protection of the equipment. The
pole ground must be sized per local utility practices to
minimize the impedance between the recloser and the
control.

IMPORTANT: All external inputs to the Form 5 con-
trol must be routed within 8 inches of their correspond-
ing ground. During a surge, a potential of approximately
1.5 kV per foot can develop in the conductors. Differ-
ences between conductor and ground path lengths can
add additional stress to the control components in the
event of a power surge.

Grounding with a Local Supply Voltage Transformer; 4-Wire Multi-Grounded,
3-Wire Ungrounded, or Impedance-Grounded