Kyle, Form 5 universal device protection (udp) control, Figure 21. interface software switch mode settings – Cooper Lighting S280-79-10 User Manual

Page 21: Figure 22. form 5/udp operator panel, Form 5/udp recloser control

background image

The UDP function allows the Form 5 control to become a
switch control to provide indication of overcurrent trip con-
ditions without issuing an overcurrent trip signal. The con-
trol is in the recloser mode when the feature is in the OFF
position, and in the switch mode when the feature is
ACTIVE.

While in the switch mode, all automatic open and close
operations of the recloser (including overcurrent voltage
and frequency) are blocked. Fault targeting, metering,
alarms, and event recording functions are active.

This non-tripping fault indication state is initiated via a
operator panel pushbutton (labeled SWITCH MODE), dig-
ital SCADA, or discrete SCADA. The UDP feature has
local indication at the operator panel (LED), digital indica-
tion, and remote indication via status contacts on the Dis-
crete Interface (DIF) module 1.

S280-79-10

21

!

SAFETY

FOR LIFE

Figure 21.
Interface software Switch Mode settings.

GND TRIP
BLOCKED

NON

RECLOSING

SUPERVISORY

BLOCKED

COLD LOAD

PICKUP

BLOCKED

BATTERY

TEST

FAST

TRIPS

DISABLED

ALTERNATE

PROFILE

NO. 1

ALTERNATE

PROFILE

NO. 2

SWITCH

MODE

Figure 20.
Function/Indication pushbuttons for the Form 5
equipped with the UDP accessory.

FORM 5 UNIVERSAL DEVICE PROTECTION (UDP) CONTROL

CONTROL OK

AC POWER

ABOVE MIN TRIP

REVERSE POWER FLOW

RECLOSER MALFUNCTION

CHECK BATTERY

BUSHINGS 1-2 FAULT TARGET

BUSHINGS 3-4 FAULT TARGET

BUSHINGS 5-6 FAULT TARGET

GROUND FAULT TARGET

SENSITIVE-GROUND FAULT TARGET

RECLOSER CLOSED

RECLOSER OPEN

CONTROL LOCKOUT

BACK

NEXT

LAMP

TEST

CHANGE

RESET

TARGETS

RESET

MAX CURRENT

GND TRIP
BLOCKED

NON

RECLOSING

SUPERVISORY

BLOCKED

COLD LOAD

PICK UP

BLOCKED

BATTERY

TEST

FAST

TRIPS

DISABLED

ALTERNATE

PROFILE

NO. 1

ALTERNATE

PROFILE

NO. 2

SWITCH

MODE

HOT LINE

TAG

ON

OFF

TX 3

RX 3

CLOSE

TRIP

(LOCKOUT)

KYLE

®

FORM 5/UDP

RECLOSER CONTROL

RS232

TX 2

RX 2

SOURCE
VOLTAGE

LOAD
VOLTAGE

Figure 22.
Form 5/UDP Operator Panel.