Kyle Form 5, Form 5 UDP, Form 5 DC NOVA Recloser Control Installation and Operation Instructions

52

Form 5 Control Default Test Optimal Values

6.

Trip Sequence

1st

2nd

3rd

4th

Ground Timing

Normal

Ground 2X

0.214

0.212

3.894

3.896

Ground 5X

0.012

0.016

1.097

1.099

Ground 10X

0.008

0.014

0.652

0.653

Profile #1

Ground 2X

0.214

0.212

3.894

3.896

Ground 5X

0.012

0.016

0.952*

0.954*

Ground 10X

0.008

0.014

0.280*

0.276*

Profile #2

Ground 2X

0.214

0.212

3.984

3.896

Ground 5X

0.012

0.016

0.952*

0.954*

Ground 10X

0.008

0.014

0.280*

0.276*

Profile #3

Ground 2X

0.214

0.212

3.894

3.896

Ground 5X

0.012

0.016

0.952*

0.954*

Ground 10X

0.008

0.014

0.280*

0.276*

7.

Enabled

Phase 2X

0.153

lockout lockout lockout

Non-Reclose

Disabled

Phase 2X

0.152

0.153

1.420

1.433

8. Cold Load

Block Off

Phase 2X

1.420

1.433

lockout lockout

PickUp Blocked

Block On

0.158

0.154

1.420

1.433

9. Fast Trips

Enabled

Phase 2X

1.419

1.422

lockout lockout

Disabled

Phase 2X

0.155

0.156

1.418

1.424

10.

No Reclose

Phase 2X

0.014

lockout lockout lockout

Hot Line Tag

Enabled

Phase 2X

0.155

0.156

1.148

1.424

11.

Reclose Sequence

1st

2nd

3rd

4th

Test Reclose

Reclose Times

1.975

1.974

4.968

lockout

12.

Fuse Out

Can’t Close?

Yes

No

Close Circuit

XXX

Disable Fuse

Fuse In

Can Close?

Yes

No

XXX

13. Instantaneous

Phase A

Phase B

Phase C

Demand Metering

Amps 80

Amps 81

Amps 80

*Refer to the Test Ground Timing section of this manual.