Kyle Form 5, Form 5 UDP, Form 5 DC NOVA Recloser Control Installation and Operation Instructions
52
Form 5 Control Default Test Optimal Values
6.
Trip Sequence
1st
2nd
3rd
4th
Ground Timing
Normal
Ground 2X
0.214
0.212
3.894
3.896
Ground 5X
0.012
0.016
1.097
1.099
Ground 10X
0.008
0.014
0.652
0.653
Profile #1
Ground 2X
0.214
0.212
3.894
3.896
Ground 5X
0.012
0.016
0.952*
0.954*
Ground 10X
0.008
0.014
0.280*
0.276*
Profile #2
Ground 2X
0.214
0.212
3.984
3.896
Ground 5X
0.012
0.016
0.952*
0.954*
Ground 10X
0.008
0.014
0.280*
0.276*
Profile #3
Ground 2X
0.214
0.212
3.894
3.896
Ground 5X
0.012
0.016
0.952*
0.954*
Ground 10X
0.008
0.014
0.280*
0.276*
7.
Enabled
Phase 2X
0.153
lockout lockout lockout
Non-Reclose
Disabled
Phase 2X
0.152
0.153
1.420
1.433
8. Cold Load
Block Off
Phase 2X
1.420
1.433
lockout lockout
PickUp Blocked
Block On
0.158
0.154
1.420
1.433
9. Fast Trips
Enabled
Phase 2X
1.419
1.422
lockout lockout
Disabled
Phase 2X
0.155
0.156
1.418
1.424
10.
No Reclose
Phase 2X
0.014
lockout lockout lockout
Hot Line Tag
Enabled
Phase 2X
0.155
0.156
1.148
1.424
11.
Reclose Sequence
1st
2nd
3rd
4th
Test Reclose
Reclose Times
1.975
1.974
4.968
lockout
12.
Fuse Out
Can’t Close?
Yes
No
Close Circuit
XXX
Disable Fuse
Fuse In
Can Close?
Yes
No
XXX
13. Instantaneous
Phase A
Phase B
Phase C
Demand Metering
Amps 80
Amps 81
Amps 80
*Refer to the Test Ground Timing section of this manual.