Sample Wiring #3 – TL- (SARGuide) with 57- (Delayed Egress)
combination and 3532 Power Supply with Battery Back-up.
Notes:
1. TL- SARGuide power requirement:
Input Power: 24VDC/VAC
Current draw: 30mA
2. Rail, raceway, electric hinge and pigtail
8 & 4-pin connector terminations and wire
colors all match.
3. If fire alarm is not required, connect the
white wire to the black (-24VDC) wire.
4. The fire alarm contact could be wired to
drop 24DC power to 57- portion of rail.
Refer to 3530 power supply instructions
for wiring.
5. Refer to 57- instructions for wiring,
specifications, operation, etc.
System Description:
SARGuide and the 57- Delayed Egress device are
always powered. During a power outage, SARGuide
remains powered and illuminated and the 57- Delayed
Egress device remains powered by the 3532 battery
back-up power.
F. TL- SARGuide Wiring Examples cont’d
Pigtail harness
assembly with
8-pin connector
Plug pigtail harness
connectors into
electric hinge
connectors
at frame side
of door
Black
(
-
24),
1
8, Yellow, Mag (+)
1
7
5
6 4
3
2
8
Green (EG), 4
Electric hinge with
8 & 4-pin connectors
Raceway harness with
8 & 4-pin connectors
7, Brown, Mag (-)
Red (+)
Normally Closed Fire
Alarm Contact
(If Required)
Red
(+24),
2
Blue (DS), 6
White (FA), 3
1584
Electromagnetic
Lock
2, Grey
(+24)
1, Violet
(
-
24)
1
4
2
3
Pigtail harness
assembly with
4-pin connector
To
TL-
To
57-
Black (-)
EXIT EXIT EX
IT
120 VAC
L/N/G
L N
Input
120VAC 60HZ
+ - + -
Output
1
Output
2
1 2 3 4 5 6 7 8 9
TB1
TB2
TB3
+
-
Battery
Battery
3532
24VDC, 2Amp
Power Supply
w/Battery Backup
GND
TL- 57- 80 Series Rail
with 8 & 4-pin
connectors
EXIT EXIT EX
IT
Copyright © 2009, SARGENT Manufacturing. All rights reserved.
Reproduction in whole or in part without the express written
permission of SARGENT Manufacturing is prohibited.
A7711C - 5-1-9