C. Changing the Master Code

1. Enter 99# to initiate programming sequence.
2. Enter current Master Code*.
3. Enter time duration: 01-90 seconds.
4. Enter 01#.
5. Enter new desired Master Code.
6. Use between a one and six digit number,

followed by a *.

7. Repeat step 5.

NOTES:

• If LED does not turn off, the code entered

has not been verified.

Press * and repeat Steps 1-6.

• If the Master Code is unknown, Programming or

Changing Mode can be entered by removing the

keypad from the outlet box and momentarily

pressing SW1 (reset button) on the circuit board.

For location, see Mounting Instructions, page 2.

• The yellow LED will flash slowly and programming

should proceed from Step 3.

Sample Programming:

D. Programming for Special Functions

1. Enter 99# to initiate programming sequence.

2. Enter Master Code*.

3. Enter Special Function Code.

91-Code operates Aux 1./Time Duration
92-Code operates Aux 2./Time Duration
98-Code operates Aux 1, and

Control Relay (Master Code duration)

4. Enter two digit time duration desired.

Enter 01 to 90 seconds for momentary Function.

Enter 00 for Maintained Passage Function.

5. Enter User Number. Enter 01# to 16#.
6. Enter Selected User Code. Use between a one

and six digit number followed by a *.

7. Repeat Step 6.

NOTES

:

1. If User Number 01# is used then its user code

is the master code.

2. Special function 98 should not be used

with User 01#.

3. AUX1 duration is common for all users of

AUX1. Changing it for one user changes

it for all users.

4. Special Function 98 uses duration set in

section "c" for Main Relay and common

duration for AUX1. Setting a duration for

Special Function 98 is ignored.

Sample Programming: