beautypg.com

4292 weather resistant mounting diagram, Caution – SARGENT 4292 Keypads User Manual

Page 5

background image

02/10/11

1-800-810-WIRE • www.sargentlock.com •

A6851J 5

Copyright © 2011, Sargen

t Manufacturing Company

, an A

SS

A AB

LO

Y G

roup company

. All right

s reser

ved

.

Reproductions in whole or in par

t without express writ

ten permission of Sargen

t Manufacturing Company is prohibited

.

4291 and 4292 Keypads

1. Do not install in any area where direct rain

will strike the keypad or where water will run

down the wall and seep into the keypad.

2. When mounting the 4292 outside, apply

silicone to the area where wires enter the

case, and install a weep hole at the bottom

of the box. This will help prevent warm air

from condensing on the circuit board.

Water shield: This shield should fold down from the top

to allow moisture to run away from the board.
Wires should be run so that they do not

interfere with the placement of the shield.

1. Wires must be protected from abrasion.
2. For use with Class II circuitry only.

NOTE: Dots ( • ) indicate wire connections.

3. Use N.C. Relay Contacts for Fail Safe Lock (nor-

mally energized). Use N.O. Relay Contacts for

Fail Secure Lock (normally de-energized).

4. Insulate any loose wires from Outlet Box and

each other.

5. When operating inductive loads such as electric

strikes and solenoid operated locks (10G70-73,

8270-73 etc.) the supplied transorb must be

installed.
For locking devices that have built in protection,

the use of the transorb is not necessary. Refer

to the literature furnished with the locking device

for this information. SARGENT 56-, 57-, 58- and
59- devices do

NOT

require use of transorb.

IMPORTANT:

The transorb must be installed as close to the

locking device as possible. This is to prevent the

electrical (inductive) kickback voltage generated

by the locking device from damaging the keypad.

4292 Weather Resistant Mounting Diagram

CAUTION:

The 4292 is not weatherproof, it is only weather

resistant. It may be installed outside, but the

following precautions must be followed.

4292 Weather Resistant Wiring Diagram Notes

Tamper resistant

screws recommended

(provided)

Wiring Harness

Gasket (provided)

Add weep hole for

wet environment

4291 or 4292

Keypad

24VDC

Transorb

Magnetic Door

Lock (Fail Safe)

+ -

NC C NO

4291 or 4292

Keypad

24VDC

Transorb

Electric Strike

(Fail Secure)

+ -

NC C NO

This manual is related to the following products: