beautypg.com

Auto-cut 300 xt – Tweco 300 XT Auto-Cut 400V User Manual

Page 138

background image

AUTO-CUT 300 XT

A-5�

APPENDIX

Manual 0-5290

238

System Bias voltage identification is invalid.

At power up the System Bias board measures the input voltage and sends signals to the CCM indicating which

range of voltage it has detected. See section 231-236 for details. If one of the 3 voltage ranges, 208-230V, 380-

415V or 480V isn’t identified then both ID signals are high resulting in an invalid signal.

Possible causes:

• Unit is connected to voltage below the 208-230V range or above the 480V range. (unlikely unless there

is a problem with the incoming voltage.)

• Defective System Bias board
• Bad connection between System Bias output J62 and CCM input J27 on the I/O board.
• Defective CCM

Troubleshooting:

1. Measure all 3 phases of the input voltage and confirm they are within the tolerance specified in the unit

manual.

2. Refer to section 231-236 Inverter VAC Mismatch and perform troubleshooting in step 1.b. If the 2 signals

don’t match the incoming voltage, if both are high, then the System Bias is defective.

3. If step 2 was OK make the same measurement at J27 on the CCM I/O PCB. If OK here the CCM is defective.

Otherwise inspect the connections at J62 and J27.

239

AC Voltage High

Voltage OK -- At power up the System Bias board measures the input voltage and determined if it is within the

range of voltage set by the J16 jumper. See section 231-236 Inverter VAC Mismatch Troubleshooting step 1.a

for details of the jumper. Normally when the input voltage is OK the System Bias board turns on a relay K1

on the left die of the board to apply power to the T1 Auxiliary transformer. D44, a green “Transformer ON”

LED, will light when K1 is energized. T1 provides power to the gas controls and the TSC 3000 as well as the

pumps and fans.

Voltage High -- If the AC voltage is determined to be too high it lights D4, ACV HIGH, a red LED on the System

Bias board, and sets the signal “AC V HIGH b” on J62-6 to a “high” about 24VDC (normal for a “low” here is

10-14VDC). To prevent the possibility of excessive voltage applied to several items (gas controls, pumps, fans

etc.) K1 is opened removing power from T1 and D44 goes off. If it’s more than a momentary glitch the gas

controls and the TSC 3000 (if used) will reset. Communication with the cutting table may be interrupted. With

the DFC 3000 Auto Gas Control and perhaps the cutting table control, the process will have to be reloaded.

D4 is on and the signal “AC V HIGH b” is high only while the voltage is actually high. The signal “AC V HIGH

b” does not latch on.

If the fault is E239 that means it is currently active, that is, currently detected as being too high. If it’s L239 that

means the voltage too high previously but it is not too high now. Applying START will clear the fault unless

it becomes active again.

The voltage that triggers an AC Voltage High fault is above 550V for 480VAC line; above 470V for a 380, 400 or

415V nominal line; above 270V for a 208 or 230VAC line.

Possible causes:

• Incoming voltage is or was too high.
• Bad connection at J62 or J27
• Bad connection at J61 jumper
• System Bias board defective
• CCM defective.