tekmar 483 tN4 Gateway User Manual
Page 10

© 2011
D 483 - 12/11
10 of 20
Alerts
A short message can be entered to use as the message 
whenever an Alert Demand is activated.
Room hot and room cold warning points can be set. 
Should the temperature exceed the hot room setting or 
the temperature fall below the cold room setting, an email 
can be sent.
Select for each user if they should be sent an email 
whenever the following occur:
External Alert Demand
- immediately
Hot room warning
- sent each hour on the hour
Cold room warning
- sent each hour on the hour
Error messages
- sent each hour on the hour
Daily status reports
- sent each day at midnight
Weekly status reports
- sent each Sunday
Temperatures
All Thermostats / Setpoint Controls Settings
Each thermostat is named after the room in which it is 
located in. Likewise, each setpoint control is named after the 
function that it operates. For each thermostat and setpoint 
control, the current temperature is shown, together with the 
current heating and cooling temperature. Click on the up 
or down button to adjust the temperature. The heat setting 
automatically increases the cooling setting if adjusted within 
3°F (1.5°C) of the cooling setting. Likewise, the cooling setting 
automatically decreases the heating setting if adjusted within 
3°F (1.5°C) of the heating setting. This prevents cycling 
between heating to cooling on the thermostat. A red box 
indicates that the thermostat is heating. Likewise, a blue 
box indicates that the thermostat is cooling.
Individual Thermostat / Setpoint Control Settings
Click on the thermostat name to access the individual 
thermostat or setpoint controls settings.
The current temperature, scene and schedule status 
are shown.
The mode can be set to Auto, Heat, Cool, or 
Off. The options available are determined by the 
thermostat model.
The Heat setpoints are available when mode is set to 
Heat or Auto.
The Cool setpoints are available when mode is set to 
Cool or Auto.
The Fan settings are available when a fan is available 
on the thermostat.
The Heat, Cool, and Fan may have multiple settings 
depending if a setback schedule is used on the 
thermostat. If no schedule is used then only the 
Occupied setting is available. If a two event schedule 
is used, then the Occupied and Unoccupied settings 
are available. If a four event schedule is used, then the 
Wake, Unoccupied, Occupied, and Sleep settings are 
available.
A green box around a setting indicates the current 
schedule event the device is operating at.
•
•
•
•
•
•
•
•
•
•
•
•
•
Alerts
Temperatures
Thermostat / Setpoint Control Settings
