Sensor wiring, Front low voltage wiring diagram, Mounting the outdoor sensor 070 – tekmar 402 House Control Installation User Manual

Page 7

background image

7 of 32

© 2010

D 402 - 09/10

R

C

L

N

Com

Open

Close

Expansion

tN4 Boil

Ct

N

4

Modulating

Boiler

—+

Expansion

tN4 Mix

Ct

N

4

2
1

WC

WC

Menu

House Control 402

Item

+

Mix

Com

Boil

Out

DHW

Vlv

C

Vlv

C

Vlv

C

Zone 3

Zone 1

Zone 2

Zone 4

Made in Canada

Vlv

C

Com

Zone 1

H800

7B

Zone 2

Zone 3

Zone 4

tN2 tN2 tN2 tN2 tN2 tN2 tN2 tN2

C

Floating Action

Cls

Opn

Sensors - No P

ow

er

Call

Call

tN4

tN4

CC

Mod dc/mA

Boil Exp.

Mix Exp.

Se
tpoint

DHW

Use at least 167°F

(75°C) conductors

R

C

Input Power

Stage 2

Stage 1

Zone Valves

24 V (ac) Transformer 009

DHW Call

from DHW

Tank Aquastat

(optional)

Setpoint Call

Outdoor

Sensor

070

Mix Supply

Sensor 082

Boiler Supply

Sensor 082

DHW Tank

Sensor 082

One or Two Stage

Boiler T-T

tekmarNet

®

2 Thermostats

24 V (ac) Floating

Action Actuator

Front Low Voltage Wiring Diagram -------------------------------------------------------------------

-------------------------------------------------------------------

Sensor Wiring

Note: The temperature sensor (thermistor) is built into the
070 enclosure.

Remove the screw and pull the front cover off the
sensor enclosure.
The 070 can either be mounted directly onto a wall or
a 2” x 4” electrical box. When the 070 is wall mounted,
the wiring should enter through the back or bottom of
the enclosure. Do not mount the 070 with the conduit
knockout facing upwards as rain could enter the enclo-
sure and damage the sensor.

In order to prevent heat transmitted through the wall
from affecting the sensor reading, it may be necessary
to install an insulating barrier behind the enclosure.
The 070 should be mounted on a wall which best rep-
resents the heat load on the building (a northern wall
for most buildings and a southern facing wall for build-
ings with large south facing glass areas). The 070
should not be exposed to heat sources such as venti-
lation or window openings.
The 070 should be installed at an elevation above
the ground that will prevent accidental damage or
tampering.

Mounting the Outdoor Sensor 070 --------------------------------------------------------------------

--------------------------------------------------------------------

Sensor with bottom
entry wiring

Sensor with rear
entry wiring

Sensor mounted
onto 2" x 4"
electrical box

tekmarNet

®

4

Expansion to

Wiring Centers,

Timers, or

User Switch