Symptom

Look For...

Corrective Action

No central
heating

Burner symbol on
LCD

If the burner symbol is on the LCD, there is a problem with the boiler. Ensure
the boiler aquastat manual limit is reset to the on position.

WWSD symbol on
LCD

Warm Weather Shut Down (WWSD) is an energy saving feature that prevents
central heating during the summer. Ensure the outdoor temperature reading
is accurate and replace outdoor sensor if necessary. WWSD setting can be
increased if heating is required.

Mix or Boil Calls on
LCD

If there are no Mix or Boil Calls, there are no thermostats calling for heat.

DHW Call on LCD

During DHW tank heating, the central heating may not be heated.

System in AWAY

During AWAY, the thermostats operate at a lower temperature. Locate a ‘User
Switch’ and set to Normal to resume heating.

“MIN” shown
together with boiler
target or boiler
supply on LCD

Boiler is operating below the boiler minimum setting and the mixing valve is
closed or the mix injection pump is operating at low speed. The mixing device
will operate normally once the boiler warms up.

Boiler short
cycling

Burner symbol
cycling on and off

Mixing using variable speed injection pumps requires the balancing valve to
be set correctly. Lack of head pressure can lead the injection pump speed to
ramp up and down.

Single zone over
heating

LCD shows zone on

Thermostats have a differential of +/- 1.5°F of the temperature setting. Due to
the display rounding numbers up, heating can appear on when the temperature
is 2°F above the setting. This is normal operation.

LCD shows zone off

Ensure zone valve terminals measure 0 V (ac). Measuring 0 V (ac) indicates
mechanical zone valve may have failed in open position. Measuring 24 V (ac)
indicates control relay may have failed.

Single zone under
heating

LCD shows zone on

Ensure zone valve terminals measure 24 V (ac). Measuring 24 V (ac) indicates
mechanical zone valve may have failed in closed position. Measuring 0 V (ac)
indicates control relay may have failed.

LCD shows zone off

Check for calls

Frequently Asked Questions (2 of 2)

Item

Setting

OUTDOOR DESIGN

MIX DESIGN

MIX TYPE

MIX MOTOR

BOILER TYPE

BOILER DESIGN

BOILER MINIMUM

BOILER MOTOR

MINIMUM MODULATION

MODULATION DELAY

Item

Setting

FLUSHING

WWSD OCCUPIED

WWSD UNOCCUPIED

DHW MODE

DHW EXCHANGE

DHW OCCUPIED

DHW UNOCCUPIED

SETPOINT

UNITS

Job Record