beautypg.com

Error messages, Step nine – tekmar 365 Mixing Control User Manual

Page 15

background image

Copyright © D 365 - 06/00

15 of 16

Step Nine

Before you leave

• Install the wiring cover over the wiring chamber and secure it to the base with the two screws provided. Place the front cover

on the control to cover the setting dials and snap it into place. Install a lock if security is required.

• Place this brochure, and all other brochures relating to the installation, in the protective plastic bag supplied with the control.

Place the bag in a conspicuous location near the control for future reference.

• It is important to explain the operation and maintenance of this control and of the system to the end user and anyone else who

may be operating the system.

• If a Boiler Return Sensor is connected and an open circuit develops, or if no sensor is installed but the "Minimum Boiler Return"

dial is set up from the off position. An error message will then be displayed (see error messages).

• If a short circuit develops at the boiler return sensor terminals, the Boiler Return function will become inactive. An error message

will then be displayed (see error messages).

After any repair has been completed, press the Test button to confirm that correct operation has been restored.

Error Messages

Whenever a fault is detected in any of the sensors, the indicator lights will flash in specific ways,
indicating the location of the problem. The following look-up table describes each error condition
and shows the flashing light sequence that results. After repairing the problem, press the Test
button to cycle the control through the test routine. This will confirm that the fault has been
repaired and that correct control action has been restored. For detailed sensor testing
instructions see Data Brochure D 001.

Light on continuously

Light flashing

Light off

Outdoor
Sensor
short
circuit
(see
trouble-
shooting
notes)

Supply
Sensor
short
circuit
(see
trouble-
shooting
notes)

Boiler
Return
Sensor
short
circuit
(see
trouble-
shooting
notes)

Boiler
Return
Sensor
open
circuit
(see
trouble-
shooting
notes)

Supply
Sensor
open
circuit
(see
trouble-
shooting
notes)

Outdoor
Sensor
open
circuit
(see
trouble-
shooting
notes)

RTU
short
circuit
(see
trouble-
shooting
notes)

10K
Indoor
sensor
short
circuit
(see
trouble-
shooting
notes)

Enclosure
Over-
heated
(see
trouble-
shooting
notes)

90

70

50

30

10

Power

WWSD

UnOcc.
Switch

Min.
Return

Boiler

Heat
Demand

Max. or
Setpoint

Pump

%

of full

output

Test

Power

WWSD

UnOcc.
Switch

Min.
Return

Boiler

Heat
Demand

Max. or
Setpoint

Pump

%

of full

output

Test

90

70

50

30

10

Power

WWSD

UnOcc.
Switch

Min.
Return

Boiler

Heat
Demand

Max. or
Setpoint

Pump

%

of full

output

Test

90

70

50

30

10

Power

WWSD

UnOcc.
Switch

Min.
Return

Boiler

Heat
Demand

Max. or
Setpoint

Pump

%

of full

output

Test

90

70

50

30

10

Power

WWSD

UnOcc.
Switch

Min.
Return

Boiler

Heat
Demand

Max. or
Setpoint

Pump

%

of full

output

Test

90

70

50

30

10

Power

WWSD

UnOcc.
Switch

Min.
Return

Boiler

Heat
Demand

Max. or
Setpoint

Pump

%

of full

output

Test

90

70

50

30

10

Power

WWSD

UnOcc.
Switch

Min.
Return

Boiler

Heat
Demand

Max. or
Setpoint

Pump

%

of full

output

Test

90

70

50

30

10

Power

WWSD

UnOcc.
Switch

Min.
Return

Boiler

Heat
Demand

Max. or
Setpoint

Pump

%

of full

output

Test

90

70

50

30

10

Power

WWSD

UnOcc.
Switch

Min.
Return

Boiler

Heat
Demand

Max. or
Setpoint

Pump

%

of full

output

Test

90

70

50

30

10