Boiler reset, Boiler reset ratio – tekmar 363 Universal Reset Control Installation User Manual

Page 6

background image

6 of 40

Copyright © D 363 -

12/08

SOFT START (SOF STRT)

The SOF STRT function allows the 363 to slowly ramp the water temperature up to the required supply temperature. By allowing the
temperature in the system to be adjusted slowly, the control reduces any thermal expansion noises and stresses that may be caused
by a quick change in supply water temperature.

WARM WEATHER SHUT DOWN (WWSD)

When the outdoor air temperature rises above the WWSD setting, the 363
turns on the

WWSD pointer in the display. When the control is in Warm

Weather Shut Down, the

Mixing Demand and Boiler Demand pointers are

displayed if there is a demand. However, the control does not operate the
heating system to satisfy these demands. The control does respond to
either a

DHW Demand or a Setpoint Demand and operates as described

in Section C.

EXERCISING (EXERCISE)

The 363 has a built-in pump and valve exercising function. The exercising period is adjustable and comes factory set at 70 hours. If a
pump or valve output on the control has not been operated at least once during every exercising period, the control turns on the output
for 10 seconds. This minimizes the possibility of a pump or valve seizing during a long period of inactivity. In the case where a mixing
valve is being used as the mixing device, the 363 ensures that the valve operates over its entire range at least once each
exercising period.

Note: The exercising function does not work if power to the control, valves or pumps is disconnected.

Section B —Boiler Reset (Mode = —1—)

Section B1 —General Boiler Operation

BOILER DEMAND

A boiler demand is generated by applying a voltage between 24 and 240
V (ac) across the

Boil Dem (4) and Com Dem (3) terminals. Once voltage

is applied, the

Boiler Demand pointer is displayed in the LCD. If the 363

is not in WWSD, it closes the Boiler Pump contact which starts the boiler
pump. The control turns on the Boil P1 segment in the LCD. The 363
calculates a Boil TRG

supply temperature based on the outdoor air

temperature and settings. The 363 then fires the boiler, if required, to
achieve and / or maintain the target supply temperature.

BOILER START (Boil STRT)

(

RESET

RATIO

)

The Boil STRT

temperature is the boiler supply water temperature that

the heating system requires when the outdoor air temperature equals the
OUT STRT

air temperature setting.

OUTDOOR START (OUT STRT)

(

RESET

RATIO

)

The OUT STRT

temperature is the outdoor air temperature at which the

control provides the Boil STRT supply water temperature

to the system.

OUTDOOR DESIGN (OUT DSGN)
(

RESET

RATIO

&

CHARACTERIZED

HEATING

CURVE

)

The OUT DSGN is the outdoor air temperature that is the typical coldest
temperature of the year where the building is located. This temperature
is used when doing heat loss calculations for the building.

70

(21)

90

(32)

110

(43)

130

(54)

150

(66)

170

(77)

190

(88)

Outdoor Air Temperature

Supply W

ater

T

emperature

210

(99)

-20

(-29)

0

(-18)

20

(-7)

40

(5)

60

(16)

80

(27)

Boil DSGN

Boil MAX

Boil MIN

OUT STRT

WWSD Unocc

Boil SETB

OUT DSGN

Boiler Reset

Ratio

WWSD Occ

Boil STRT

Section B2

Alternate Boiler

Demands

Section B1

General Boiler

Operation