Menus, View menu – tekmar 363 Universal Reset Control Installation User Manual

Page 23

background image

23 of 40

Copyright © D 363 -

12/08

Minimum boiler supply temperature during a setpoint
demand.

10K 2 = DHW,

OR

DHW THRU = NONE

363 View Menu (1 of 1)

-31 to 266˚F
(-35 to 130˚C)

- - -, OFF, 70 to 220˚F
(OFF, 21 to 104˚C)

Current DHW tank temperature.

10K 2 = DHW
DHW THRU

≠ NONE

Section

LT

D

USER INST ADV

C1

C4

Range

Access
Level

Description

Current outdoor air temperature as measured by the outdoor
sensor. This is the default display for the control.

-67 to 149˚F
(-55 to 65˚C)

Target room air temperature. “– – –” denotes no heat is
required.

10K 1 = INDR

- - -, 35 to 100˚F
(2 to 38˚C)

D3

Measured room air temperature at the indoor sensor.

10K 1 = INDR

-58 to 167˚F
(-50 to 75˚C)

D3

This is the signal that is being received from a tekmar Zone
Control that is operating mixing zones.

10K 1 = MIX

- - -, 35 to 110˚F
(2 to 43˚C)

D3

This is the signal that is being received from a tekmar Zone
Control that is operating the boiler zones.

10K 1 = Boil

- - -, 35 to 110˚F
(2 to 43˚C)

B2

Current slab sensor temperature.

10K 1 = SLAB
MIX MIN = OFF

-58 to 167˚F
(-50 to 75˚C)

D3

Target mixed supply is the temperature the control is
currently trying to maintain at the mixing sensor.

- - -, 35 to 248˚F
(2 to 120˚C)

D1

Current mixed supply water temperature as measured by
the mixing sensor.

-31 to 266˚F
(-35 to 130˚C)

D1

Target boiler supply is the temperature the control is currently
trying to maintain at the boiler sensor +/- 1/2 of the
differential.

- - -, 35 to 248˚F
(2 to 120˚C)

B1

Current boiler supply water temperature as measured by
the boiler sensor.

-31 to 266˚F
(-35 to 130˚C)

Current storage tank temperature as measured by the
storage tank sensor.

10K 2 = STOR

-31 to 266˚F
(-35 to 130˚C)

E2

Minimum boiler supply temperature during a DHW demand.

10K 2

≠ DHW

DHW THRU

≠ NONE

- - -, OFF, 100 to 220˚F
(OFF, 38 to 104˚C)

C1

Target DHW tank temperature.

10K 2 = DHW
DHW THRU

≠ NONE

- - -, OFF, 70 to 190˚F
(OFF, 21 to 88˚C)

C1

B1

Item Field