tekmar 363 Universal Reset Control Installation User Manual
Page 25

25 of 40
Copyright © D 363 -
12/08
363 Adjust Menu (2 of 5)
•
•
D1
The starting water temperature used in the reset
ratio calculation for the mixed supply.
DIP switch =
Reset Ratio
35 to 150˚F
(2 to 66˚C)
Default = 70
°F (21°C)
D1
•
•
The design supply temperature used in the heat
loss calculation for the mixing system.
70 to 220˚F
(21 to 104˚C)
Default = 120
°F (49°C)
D1
•
•
The outdoor starting temperature used in the
reset ratio calculation for the heating system.
DIP switch =
Reset Ratio
35 to 85˚F
(2 to 29˚C)
Default =70
°F (21°C)
B1
D1
•
•
The design outdoor air temperature used in the
heat loss calculation for the heating system.
-60 to 32˚F
(-51 to 0˚C)
Default = 10
°F (-12°C)
D1
•
•
The maximum supply
target temperature for the
mixing system.
80 to 210˚F, OFF
(27 to 99˚C, OFF)
Default = 140
°F (60°C)
D2
•
•
The type of mixing device that is to be used in
the heating system.
FLOT (Floating),
VAR (Variable speed),
STOR (Storage)
Default = VAR
•
•
D2
The time that the actuating motor requires to
operate from fully closed to fully open.
MIXING = FLOT
30 to 230 sec
Default = 160 sec
•
•
C1
The device that is to be connected to the 10K 2
input terminal.
NONE, DHW, STOR
(Storage tank)
Default =
NONE
E3
The polling time that is to be used for a storage
tank.
MIXING = STOR
10K 2
≠ STOR
0:20 to 12:00 hr
Default = 1:00 hr
•
•
•
•
D1
The design indoor air temperature used in the
heat loss calculation for the mixing system.
DIP switch =
Characterized Heating Curve
35 to 100˚F
(2 to 38˚C)
Default =70
°F (21°C)
Actual
Setting
Section
LT
D
INST ADV
Range
Access
Level
Description
Item Field
USER