363 Schd (Schedule) Menu (1 of 1)
•
•
•
•
A
The type of setback override that is in effect.
DIP switch =
Setback
AWAY is available even if DIP ≠ Setback
NONE, TMPY Occ Ovr, PERM Occ
Ovr, TMPY UnOcc Ovr, PERM
UnOcc Ovr, AWAY Ovr
Default = NONE
Section
LT
D
INST ADV
Range
Access
Level
Description
Item Field
USER
The frequency with which the control will exercise
the pumps and valves that are operated by
the control.
363 Adjust Menu (5 of 5)
•
•
•
•
C4
A
A
B1
•
A
•
A
•
C4
•
•
•
•
•
•
Selects whether or not a setpoint demand will be
responded to during the UnOccupied period.
DIP switch =
Setback
10K 2 = DHW,
OR
DHW THRU = NONE
Selects whether or not the setpoint demand will
have priority over the heating system.
10K 2 = DHW,
OR
DHW THRU = NONE
The system’s warm weather shut down during the
Occupied period.
The system’s warm weather shut down during the
UnOccupied period.
DIP switch =
Setback
The maximum length of time that the boiler pump
will continue to run after the boiler demands have
been removed.
The portions of the heating system that will use
the Soft Start feature.
OFF, SETPOINT Occ
Default = OFF
NONE, B+M
(Boiler + Mixing)
Default = NONE
35 to 100˚F, OFF
(2 to 38˚C, OFF)
Default = 70°F (21°C)
35 to 100˚F, OFF
(2 to 38˚C, OFF)
Default = 60 °F (16°C)
OFF, 0:10 to 40:00 min
Default = 0:20 min
NONE, MIX, B+M
(Boiler + Mixing)
Default = NONE
30 to 240 hr, OFF
Default = 70 hr
UnOcc
Occ
UnOcc
Actual
Setting
Section
LT
D
INST ADV
Range
Access
Level
Description
Item Field
USER