Error messages – tekmar 363 Universal Reset Control Installation User Manual

Page 35

background image

35 of 40

Copyright © D 363 -12/08

The number of times that a communication error has been detected

between the control and either an RTU or RDM since this item

was last cleared. If the wires between the control and either the

RTU or RDM are run in a noisy electrical environment, this can

cause interference in the communication between the control and

the RTU or RDM.

363 Monitor Menu (3 of 3)

0 - 255

0 - 255

0 - 255

The number of times that the microprocessor in the control has

had to reset itself since this item was last cleared. The control will

reset itself if it has experienced some form of interference that

has disrupted its operation. This can be used to give an indication

of the quality of the electrical environment that the control has

been installed in.

The number of times the control has been powered up since this

item was last cleared. This number will increase if there is a lowering

of the input voltage beyond the control’s usable range. This item

can be used as an indication of the quality of the power source.

USER

LTD

INST ADV

Range

Access

Level

Description

Item Field

Note: To clear the recorded information in the specific Item field, press and hold and .

r

o

r

r

E

f

o

n

o

it

p

i

r

c

s

e

D

d

e

y

a

l

p

s

i

D

r

o

r

r

E

363 Error Messages (1 of 4)

The control was unable to store a piece of information into its EEPROM. This error can be caused by

a noisy power source. The control will display the error message and will continue to operate as normal.

Pressing either the Menu or Item button will clear this error.

The control was unable to read a piece of information stored in the Adjust menu. Because of this, the

control was required to load the factory settings into all of the items in the Adjust menu. The control

will stop operation until all of the items available in the Adjust menu of the control have been checked

by the user or installer.

Note: Access level must be ADV in order to clear the error.

The control was unable to read a piece of information stored in the Monitor menu. Because of this,

the control was required to load the factory settings into all of the items in the Monitor menu. The

control will continue to display the error message until all of the items available in the Monitor menu

of the control have been checked by the user or installer.

Note: Access level must be ADV in order to

clear the error.

The control was unable to read a piece of information stored in the Miscellaneous menu. Because of

this, the control was required to load the factory settings into all of the items in the Miscellaneous

menu. The control will continue to display the error message until all of the items available in the

Miscellaneous menu of the control have been checked by the user or installer.

Note: Access level must

be ADV in order to clear the error.

The RTU was unable to store a piece of information to the EEPROM. This error can be caused by a

noisy power source to the control. The control will display the error message and will continue to

operate as normal. Pressing either the Menu or Item button will clear this error.

The control was unable to read a piece of information stored in the Schedule menu. Because of this,

the control was required to load the factory settings into all of the items in the Schedule menu. The

control will continue to display the error message until all of the items available in the Schedule menu

of the control have been checked by the user or installer.

Note: Access level must be ADV in order to

clear the error.