Adjust menus – tekmar 363 Universal Reset Control Installation User Manual
Page 24
24 of 40
Copyright © D 363 -
12/08
•
D1
•
•
•
•
•
•
•
D1
D3
B2
B2
D3
•
•
•
D3
•
•
A
•
•
•
•
•
D1
•
•
A
363 Adjust Menu (1 of 5)
Occ
D1
The desired room air temperature during an
Occupied period for mixing zone(s).
Note: There
is only a
±3°F adjustment in the LTD access level.
DIP switch =
Characterized Heating Curve
No RTU connected
35 to 100˚F
(2 to 38˚C)
Default = 70
°F (21°C)
35 to 100˚F
(2 to 38˚C)
Default = 65
°F (18°C)
UnOcc
The desired room air temperature during an
UnOccupied period for mixing zone(s).
DIP switch =
Characterized Heating Curve
DIP switch =
Setback
No RTU connected
•
•
NONE, INDR (Indoor),
MIX (Mixing zone
control), Boil
(Boiler
zone control), SLAB
Default = NONE
•
•
NONE, Boil (Boiler
zone control)
Default = NONE
The device that is to be connected to the 10K 1
input when an RTU is not connected.
DIP switch =
Characterized Heating Curve
No RTU connected
The device that is to be connected to the 10K 1
input when an RTU is connected.
DIP switch =
Characterized Heating Curve
RTU is connected
OFF, 35 to 120˚F
(OFF, 2 to 49˚C)
Default = 70
°F (21°C)
40 to 150˚F
(4 to 66˚C)
Default = 90
°F (32°C)
The minimum temperature at the slab sensor
DIP switch =
Characterized Heating Curve
No RTU connected
10K 1 = SLAB
OFF, 0:20 to 8:00 Hr.
Default = OFF
The maximum temperature at the slab sensor.
DIP switch =
Characterized Heating Curve
No RTU connected
10K 1 = SLAB
The
maximum length of morning boost.
DIP switch =
Characterized Heating Curve
DIP switch =
Setback
No RTU connected
10K 1
≠ MIX
The amount the mixing supply water temperature
will be reduced when the control is in the
UnOccupied mode.
DIP switch =
Reset Ratio
DIP switch =
Setback
0 to 50˚F
(0 to 28˚C)
Default = 9
°F (5°C)
The type of terminal units that are being used for
the mixing side of the system.
DIP switch =
Characterized Heating Curve
HRF1 (Heavy), HRF2
(Light), (Fan-) COIL,
CONV (ector), RAD
(iator), BASE (board)
Default = HRF1
The minimum supply water temperature for the
mixing system.
DIP switch =
Characterized Heating Curve
OFF, 35 to 150˚F
(OFF, 2 to 66˚C)
Default = OFF
Actual
Setting
Section
LT
D
INST ADV
Range
Access
Level
Description
Item Field
USER