Item Field

Range

Description

Actual Setting

2 to 45°F

(1 to 25°C)

Default = 10°F

(5.5°C)

MAXIMUM STORAGE DIFFERENTIAL
The variable speed pump will turn back on when
the storage temperature falls this differential below
the Max Storage Target.

70 to 190°F

(21 to 88°C)

Default = 140°F

(60°C)

MINIMUM STORAGE TARGET
(Mode 2)
The supplemental heat pump, P2, will turn on when
the storage temperature falls below this target.
Optional Auxiliary Sensor.

2 to 45°F

(1 to 25°C)

Default = 10°F

(5.5°C)

MINIMUM STORAGE DIFFERENTIAL
(Mode 2)
The supplemental heat pump will turn off when the
storage temperature rises this differential above the
Min Storage Target. Optional Auxiliary Sensor.

190 to 260°F,

OFF

(88 to 127°C,

OFF

Default = OFF

MAXIMUM SOURCE TARGET

The variable speed pump will turn off if the source
temperature rises above the Maximum Source
Target. See Table 3 for Mode 3 operation.

2 to 45°F

(1 to 25°C)

Default = 10°F

(5.5°C)

MAXIMUM SOURCE DIFFERENTIAL
(Maximum Source Target ≠ Off)
The heat dump pump will turn off when the
storage temperature falls this differential below
the Maximum Source Target.

OFF, 50 to

185°F

(OFF, 10 to

85°C)

Default = OFF

MINIMUM SOURCE TARGET
If the source temperature drops below this setpoint
the injection pump is turned off

2 to 45°F

(1 to 25°C)

Default = 10°F

(5.5°C)

MINIMUM SOURCE DIFFERENTIAL
(Min Source Target ≠ Off)
The variable speed pump will turn back on when
the source temperature rises this differential above
the Minimum Source Target.

50 to 220°F

(10 to 104°C)

Default = 100°F

(38°C)

MAXIMUM AUXILIARY TARGET
(Mode 3)
The heat dump pump will turn off when the auxiliary
temperature rises above this target.

2 to 45°F

1 to 25°C

Default = 10°F

(5.5°C)

MAXIMUM AUXILIARY DIFFERENTIAL
(Mode 3)
The heat dump pump will turn on when the
auxiliary temperature falls this differential below
the Maximum Auxiliary Target.

ON, OFF

Default = OFF

FREEZE PROTECTION
(Mode ≠ 4)
If the source temperature falls below 35°F (2°C),
the variable speed pump will turn on at 100% output
until the source temperature rises to 40°F (4°C).

Adjust Menu (2 of 3)