Wiring Diagrams
5-pin Euro-Style Hookup
Wiring the 5-pin Euro-style connector depends on the model and power requirements of the device. Connecting dc power to the commu-
nication pins will cause permanent damage.
Wire No.
Wire Color
Description
1
Brown
10 to 30V dc
2
White
RS485 / D1 / B / +
3
Blue
dc common (GND)
4
Black
RS485 / D0 / A / –
5
Gray
Comms Gnd
Terminal Block (IP67 Housing)
When your wireless network does not include a host system, the eight input/four output Gateway must be mapped to the four input/eight
output Node. Connecting dc power to the communication pins will cause permanent damage.
PWR
GND
PWR
GND
DO4
DO3
DO2
DO1
DI8
DI7
DI6
DI5
DI4
DI3
DI2
DI1
DIx. Discrete IN x.
DOx. Discrete OUT x.
GND. Ground/dc common connection.
PWR. Power, 10 to 30V dc power connection.
DX80...C Wiring
Wiring power to the DX80...C models varies depending the power requirements of the model.
Terminal Label Gateway, DX85 *
10 to 30V dc Powered Nodes
Battery Powered Nodes **
V+
10 to 30V dc
10 to 30V dc
Tx/+
RS485 / D1 / B / +
V-
dc common (GND)
dc common (GND)
dc common (GND)
Rx/-
RS485 / D0 / A / -
B+
3.6 to 5.5V dc
* Connecting dc power to the communication pins will cause permanent damage.
** For FlexPower devices, do not apply more than 5.5V to the gray wire.
Terminal Block (IP20 Housing)
When your wireless network does not include a host system, the eight input/four output Gateway must be mapped to the four input/eight
output Node. Connecting dc power to the communication pins will cause permanent damage.
SureCross DX85 Modbus RTU Remote I/O Device
P/N 134324 rev. F