Banner SureCross DX80 Wireless Networks User Manual
Page 4

Analog Configuration, Switch 2 OFF
DIP Switches
Descriptions
3
4
5
6
7
8
Sample/Report Rate 64 seconds
ON
OFF
OFF
Sample/Report Rate 5 minutes
ON
OFF
ON
Modbus or UCT configured (overrides DIP switches)
ON
ON
OFF
Sample/Report Rate 15 minutes
ON
ON
ON
Analog IN 2 (not available in integrated battery model), Discrete 1, and Discrete 2 are not powered from switched power terminals. In this
configuration, SP2 is disabled. If you need SP2, contact the factory.
Boost Voltage
The boost voltage is the power supplied to the sensor powered by this FlexPower Node.
Modbus/User Configuration Tool (UCT) or DIP Switch Configured
In Modbus/UCT Configured mode, the device parameters are changed using the User Configuration Tool (UCT) or a Modbus command.
All DIP switch positions are ignored. In DIP Switch Configured mode, use the DIP switches to configure the parameters listed in the table.
Sample and Report Rates
The sample interval, or rate, defines how often the SureCross device samples the input. For battery-powered applications, setting a slow-
er rate extends the battery life.
The report rate defines how often the Node communicates the I/O status to the Gateway. Change of state reporting sets the system to
report only when the value crosses the threshold setting. For FlexPower™ applications, setting the report rate to a slower rate extends
the battery life.
Warm-Up Time
The warm-up time defines how long the device must power up the sensor before a stable sensor reading is taken.
DIP Switch Settings for Discrete Configuration (DIP Switch 2 ON)
The discrete configuration matches the switch power outputs (SP1, SP2) with the discrete inputs. The discrete configuration is selected
when switch 2 is in the ON position. Two sinking discrete outputs are active for this configuration.
Discrete Configuration, Switch 2 ON
DIP Switches
Descriptions
3
4
5
6
7
8
Discrete Sinking (NPN)
OFF*
Discrete Sourcing (PNP)
ON
Boost Voltage: 5V
OFF*
Boost Voltage: 10V
ON
Warm-up Time 4 milliseconds
OFF*
Warm-up Time 10 milliseconds
ON
Sample/Report Rate 62.5 milliseconds
OFF
OFF
OFF
Sample/Report Rate 125 milliseconds
OFF
OFF
ON
Sample/Report Rate 250 milliseconds
OFF
ON
OFF
Sample/Report Rate 500 milliseconds
OFF
ON
ON
Sample/Report Rate 1 second
ON
OFF
OFF
Sample/Report Rate 2 seconds
ON
OFF
ON
Modbus or UCT configured (overrides DIP switches)
ON
ON
OFF
Sample/Report Rate 16 seconds
ON
ON
ON
Discrete IN 1 uses switched power 1 (SP1). Discrete IN 2 uses switched power 2 (SP2).
SureCross DX80 FlexPower Node
4
www.bannerengineering.com - tel: 763-544-3164
P/N 131296 Rev. L