Dynamic Braking Kits for FlexPak 3000 and WebPak 3000 Digital DC Drives

11

If you are using DB with a Motor Series Field, S1 connected to A2

with an Inverting Fault Circuit

Breaker:

Step 1. Follow the wiring diagram in figure 8 to connect the motor armature and the Dynamic Braking Resistor

assembly to the FlexPak 3000 drive.

Step 2. Remove the Removable Link (see figure 6). It is a bus section below the A2/S1 terminal and is

accessed through the top of the drive as shown. At the top, the A2/S1 terminal and Removable Link
are fastened with two nuts and bolts, spaced horizontally. Remove them and set them aside along
with the A2/S1 terminal for subsequent re-installation. At the bottom, remove the two bolts spaced
vertically and set them aside. Take the Removable Link (bus section) out of the drive.

Step 3. Replace the lower two vertically-spaced bolts and tighten to 23 Nm (200 in-lb).

Step 4. Replace the A2/S1 terminal fastening it with the upper two horizontally-spaced nuts and bolts

previously removed. Tighten to 23 Nm (200 in-lb).

Step 5. Route the resistor assembly harness as required. Use M10 x 25 mm screws, nuts and washers to

attach resistor assembly harness to DBR and A2/S1 connections on the drive. See figure 8.

Step 6. Connect the Inverting Fault Circuit Breaker kit to the DRV and MOT terminals as shown. Ignore the

dashed-line connection.

Step 7. Route the customer-supplied wire (cable) and attach to the connections A2/S1 and Motor A2 (or

Motor S1) as shown.

Step 8. Connect the Series Field between the terminals Motor S1 and Motor S2.

Step 9. Follow the wiring diagram in figure 5 to verify that the jumper across terminals 3 and 4 on the FIELD/

DB terminal block is installed.

Step 10. Remove the lockout and tag from the power to the drive.

Step 11. Turn on power to the drive.

If you are using DB with a Motor Series Field, S1 connected to A2

without an Inverting Fault Circuit

Breaker:

Step 1. Follow the wiring diagram in figure 8 to connect the motor armature and the Dynamic Braking Resistor

assembly to the FlexPak 3000 drive.

Step 2. Remove the Removable Link (see figure 6). It is a bus section below the A2/S1 terminal and is

accessed through the top of the drive as shown. At the top, the A2/S1 terminal and Removable Link
are fastened with two nuts and bolts, spaced horizontally. Remove them and set them aside along
with the A2/S1 terminal for subsequent re-installation. At the bottom, remove the two bolts spaced
vertically and set them aside. Take the Removable Link (bus section) out of the drive.

Step 3. Replace the lower two vertically-spaced bolts and tighten to 23 Nm (200 in-lb).

Step 4. Replace the A2/S1 terminal fastening it with the upper two horizontally-spaced nuts and bolts

previously removed. Tighten to 23 Nm (200 in-lb).

Step 5. Route the resistor assembly harness as required. Use M10 x 25 mm screws, nuts and washers to

attach resistor assembly harness to DBR and A2/S1 connections on the drive. See figure 8.