Assign an ip address to the kinetix 5500 drive, Assign an ip address to, The kinetix 5500 drive – Rockwell Automation Logix5000 Control Systems: Connect Kinetix 5500 Drives on EtherNet/IP Network Quick Start User Manual
Page 29

Rockwell Automation Publication IASIMP-QS035A-EN-P - December 2012
29
Prepare the Kinetix 5500 Drive Hardware Chapter 1
Assign an IP Address to the Kinetix 5500 Drive
You can assign an IP address to the Kinetix 5500 drive manually via the drive keypad or dynamically via a
DHCP-enabled server. Because this publication describes tasks intended to be completed on a private network,
you assign an IP address.
The Kinetix 5500 drive has two status indicators and an LCD status display. The indicators and display are used
to monitor the system status, set network parameters, and troubleshoot faults. Four navigation buttons are
located directly below the display and are used to select items from a soft menu.
You program network parameters by using the LCD display and navigation buttons.
1.
From the LCD display, select SETUP>NETWORK and choose STATIC IP.
The default network setting is STATIC IP with an IP address of 192.168.1.1.
2.
Press
to configure the following parameters:
•
IP address
•
Gateway
•
Subnet mask
3.
Cycle 24V control power.
Settings are stored in nonvolatile memory. IP addressing may also be changed through the Module
Configuration dialog box in RSLinx® software. Refer to the Kinetix 5500 Servo Drives User Manual,
publication
IMPORTANT
Changes to the IP addressing take effect only after cycling 24V control power.
PRECHARAGE
192.168.1.1
DC BUS: 0.3V
SETUP
MENU
SETUP
MENU
PRECHARGE
192.168.1.1
DC BUS: 0.3V
Soft Menu
Navigation Buttons
Status Indicators