Rockwell Automation SA3100 AC Power Modules User Manual
Page 61

Technical Specifications
A-7
575 VAC Output Drives
C/W 001
2.5
C/W 003
6
C/W 007
10
91
217
308
C/W 010
12
103
251
354
C/W 015
19
117
360
477
C/W 020
24
140
467
607
C/W 025
30
141
492
633
C/W 030
35
141
526
667
C/W 040
45
175
678
853
C/W 050
57
193
899
1092
C/W 060
62
193
981
1174
C/W 075
87
Fig A.18
361
1553
1894
C/W 100
109
Fig A.19
426
1978
2504
C/W 125
138
Fig A.20
522
2162
2683
C/W 150
160
Fig A.21
C/W 200
252
Fig A.22
755
3065
3820
C/W 250
284
Fig A.23
890
3625
4515
C/W 300
5
298
None
926
5015
5941
C/W 350
354
None
1000
5935
6935
C/W 400
406
Fig A.24
1430
7120
8550
C/W 450
460
Fig A.25
1465
8020
9485
C/W 500
505
Fig A.26
1500
8925
10425
C/W 600
600
Fig A.27
1610
10767
12377
C/W 650
673
Fig A.28
1700
12000
14000
W 800
800
None
1. Base Amps with nominal input voltage (240, 480, or 600V). If input voltage exceeds rating, drive output
must be derated. Refer to figure A.30.
2. Drive ambient temperature rating is 40° C. If ambient temperature exceeds 40° C, the drive must be
derated. Refer to figures A.1 to A.28.
3. Drive rating is based on altitudes of 100 m (3300 ft) or less. If installed at a higher altitude, drive must be
derated. Refer to figure A.29.
4. Not available at time of publication.
5. Important: Two (2) 725 CFM fans are required if an open type drive is mounted in a user-supplied
enclosure.
Table A.2 – Enclosure Requirements
Power
Module
Model No.
Base
Derate
Amps
1
Derating
Curve
2,3
Heat
Dissipation
Watts
2,3
Heatsink
Watts
2
Total
Watts
2