Build and Install the Cables

Correct cable routing and careful cable construction improves system electromagnetic
compatibility (EMC).

Follow these guidelines to build and install the cables:

Keep the wire lengths as short as possible.

Route noise sensitive wiring (encoder, serial, and I/O) away from input power and motor
power wiring.

Separate cables by 0.3 m (1 ft) minimum for every 9 m (30 ft) of parallel run.

Ground both ends of the encoder cable shield and twist the signal wire pairs to prevent
EMI from other equipment.

ATTENTION: High voltage can be present on the shield of a power cable, if the shield is not grounded.

Verify that there is a connection to ground for any power cable shield.

ATTENTION: MP-Series motors produce leakage current in the protective earthing conductor that exceeds
3.5 mA AC and/or 10 mA DC.

Be sure to properly ground the motor cables per the drive installation instructions.