Monitored Digital Input Modules (T3411)


6

Industrial Control Services

green ACTIVE indicator flashes at the controller's scan rate.
If a module fault occurs the red FAULT indicator turns on
and the green indicator turns off.

Power Status Indicator

The POWER GOOD LED indicates the presence of field
voltage at the module’s field power input terminals and the
overall health of the module’s field power regulator circuits.

Input Status Indicators

Input status indicators show contact and line status for each
point.

A yellow contact status indicator is turned on when the
contact is closed or the line has shorted.

A red line status indicator is turned on when the field wiring
is open circuit or short circuit. If line monitoring is not
desired, this LED can be disabled (see Disable Fault LED,
page 20 for more details).