Monitored Digital Input Modules (T3411)


2 4

Industrial Control Services

If energize-to-trip inputs are used in safety critical
applications, line monitor devices must be installed at the
field switches. The Fault Name variables must be configured
and line fault status must be alarmed to plant operations
personnel.

For de-energize-to-trip inputs, line monitor devices are
recommended in order to detect the difference between a
normally closed input and a shorted field wire.

For additional safety considerations, please refer to the Safety
Considerations section of the Regent User’s Guide.

Specifications

Safetybus Power

0.85 load units

Number of Inputs

16, common power return

Field Power

Voltage:

Current:

15 to 80 VDC

450 mA, maximum

Turn-On Voltage (default)

> 12 Vdc

Turn-Off Voltage (default)

< 12 Vdc

Input Current

5.0 mA, maximum

Turn-On Delay

10 msec, maximum

Turn-Off Delay

10 msec, maximum

Over Voltage Protection

Field Power Terminals:

Input Terminals:

100 Vdc continuous

27 Vdc continuous

Heat Dissipation

8.5 Watts, 29 BTUs/hour

Fusing

None required, internal
resistor limits current to
5 mA if input short circuit.

Isolation

2500 volts minimum (field
wiring to control logic)

Input Circuit Test Interval

Function of application
program scan time and size
of I/O configuration.
Typically less than 2 seconds
(see page 5 for details).