Monitored Digital Input Modules (T3411)


P D - 6 0 3 1 M a r - 0 6

21

Field wiring open circuit or short circuit conditions are
referenced in the application program using the Fault Name
tag names defined in the I/O configuration Editor. When a
line monitor device is installed across the field switch and the
wiring is healthy, the Fault Name status is on. If there is a
short or open circuit (or there is no line monitor device
installed) the Fault Name status is off.

The status of the Name and Fault Name input variables are
summarized in Table 3 for the various field input conditions.

Table 3. Input Status for Field Input Conditions.

With Line Monitor Device

Installed

Without Line Monitor

Device Installed

Field Input
Condition

Name

Fault Name

Name

Fault Name

Switch Open

OFF

ON

OFF

OFF

Switch Closed

ON

ON

ON

OFF

Open Circuit

OFF

OFF

Same as Switch Open

Short Circuit

ON

OFF

Same as Switch Closed

Programming Dual Fault Tolerant Monitored Inputs

To program fault tolerant configurations using dual
monitored input modules, ladder logic is used to check the
status of the inputs and the system control relays (that report
a faulted I/O module) and provide a voted input value. Two
examples are shown below.

Normally Energized Inputs

Figure 14 shows a ladder logic rung that would be suited for
normally energized inputs that de-energize to trip.

Figure 14. Dual Voting for Normally Energized Inputs.