ICS Regent

®

PD-6031

Industrial Control Services

1

Monitored Digital Input Modules

24 VDC

(T3411)

Issue 1, March, 06

Monitored digital input modules provide input sensing for 16
field input devices. With a line monitor device installed at the
field switch, monitored digital input modules detect input
switch status and field wiring open and short circuits. Input
and line status are reported back to the controller for use in
application program logic.

Features

·

Sixteen input points.

·

Fault tolerant operation when connected in parallel with

another module of the same type.

·

Hot-replaceable.

Complete, automatic testing of all input circuits.

Automatic line monitoring detects open and short field wiring

faults.

·

Individual front panel indicators on each module show the

module’s active/fault and power status, as well as input status
and line fault status for each point.

·

2500 volt minimum electrical isolation between field and logic

circuits.

·

TÜV certified, Risk Class 5.

The input module circuits are completely and automatically
tested, providing a fail-safe interface for safety-critical inputs.
Two or three monitored digital input modules can be
connected in parallel to obtain fault tolerant input sensing.
In these fault tolerant configurations, a failed module can be