Install swing-out latch brackets – Rockwell Automation 2100 CENTERLINE Motor Control Center (MCC) Units with Horizontal Operating Handl User Manual
Page 6
![background image](/manuals/580676/6/background.png)
6
Rockwell Automation Publication 2100-IN060D-EN-P - March 2014
CENTERLINE 2100 Motor Control Center (MCC) Units with Horizontal Operating Handles
See additional instructions in the table.
Non ArcShield Unit Support Pan Installation
ArcShield Unit Support Pan Installation
10. Replace the isolation barrier if one was removed.
Install Swing-out Latch
Brackets
Swing-out latch brackets are used on all latch positions for all units with
horizontal handles.
1. Working from the inside of the vertical wireway cutout, place the
swing-out latch bracket on the back of the front flange of the right hand
unit support.
For
Follow This Step
Non ArcShield units
Insert the white plastic retaining clip through the holes in the vertical wireway
wall and pan, working from inside the vertical wireway as shown. See
ArcShield Unit Support Pan Installation
.
All ArcShield units
Secure the unit support pan to the right-hand unit support with the ¼-20
self-tapping screw supplied with the bracket and tighten to 55 lb•in (6 N•m)
with a 3/8 in. socket wrench. See
ArcShield units with 100 ms arc
duration rating
Secure the left-rear corner of the unit support pan with a 10-32 self-tapping
screw and tighten to 32 lb•in. (3.6 N•m) using a 5/16 in. socket wrench.
Plastic
Retaining Clip
Unit Support Pan
Unit Support Pan
Screw
Arc Resistant
Latch
Bracket
Arc
Resistant
Latch
Bracket
Screw
Unit Support Pan