PowerBrick™ Installation
Chapter 3
Power Connections
1. The PowerBrick units are connected to each other in order to create a
complete phase assembly. The flexible connector on the top of each
PowerBrick is attached to the fixed connector on the bottom of the
PowerBrick above.
2. The top PowerBrick should be connected to a suitable fixed terminal
location. Use appropriate cable lugs to attach suitable line cables to the line
cable terminal. Each PowerBrick can use M10 (3/8 in.) hardware. Refer to
for the terminal location. Torque the fastening hardware to the
3. Use cable lugs to attach suitable load cables to the load cable terminal
(lower). Refer to
for the terminal location. Torque the fastening
hardware to the specifications shown in
4. Refer to
and
for a typical wiring diagram to
determine the required connections.
includes a typical
schematic for a complete soft starter unit.
ATTENTION: To avoid shock hazard, lock out incoming power to power cables
when completing connections. Failure to do so may result in severe burns,
injury or death.
IMPORTANT
It is the responsibility of the OEM to ensure that suitable line and load cables
are used to satisfy the requirements of the equipment and meet local electrical
codes.