Dimensions, Torque requirements, Powerbrick mounting – Rockwell Automation 7703E Medium Voltage SMC OEM Components - 10-15 kV User Manual
Page 13: Dimensions torque requirements powerbrick mounting
Rockwell Automation Publication 7703E-IN001E-EN-P - July 2014
13
PowerBrick™ Installation
Chapter 3
Dimensions
Refer to
, and
for PowerBrick dimensions and
mounting.
Torque Requirements
All electrical connections must be torqued to the specifications shown in
.
Table 4 - Torque Requirements
PowerBrick Mounting
PowerBricks are to be mounted in a vertical orientation in order to provide
adequate component cooling. Mount the PowerBricks in a suitable location using
the mounting holes provided in the assembly (refer to
). Use
M8 (5/16 in.) or similar hardware for the mounting hole dimensions of
10.7 x 15.9 mm (0.421 x 0.625 in.).
PowerBricks are provided with two methods for mounting (as shown in
). The PowerBricks can be mounted to a vertical surface using the four
mounting locations on the rear face, or they can be mounted to a horizontal
surface using the four mounting locations on the base.
Note: Using either mounting option requires space above and below each phase
assembly (refer to
ATTENTION: Ensure that all electrical connections are torqued to the correct
specification. Failure to do so may result in damage to the equipment and/or
injury to personnel.
Hardware
Recommended Torque
¼-20 thread cutting housing assembly screws
7 N•m [62 lb•in]
M5
3.4 N•m [30 lb•in]
Control Wire Terminals
0.2…0.4 N•m [2.0…3.3 lb•in]
CLGD Power Assembly Terminals
5.6 N•m [50 lb•in]
SMC Flex Control Module Terminals
0.6 N•m [5in•lb]
M8, Capacitor Lugs
M8, All others
7.5 N•m [66 lb•in]
14 N•m [120 lb•in]
M10
29 N•m [250 lb•in]