Sizing the enclosure – Rockwell Automation 7703E Medium Voltage SMC OEM Components - 10-15 kV User Manual
Page 12

12
Rockwell Automation Publication 7703E-IN001E-EN-P - July 2014
Chapter 3
PowerBrick™ Installation
In addition to the PowerBricks, a voltage sensing board is to be connected in the
power circuit.
lists the voltage sensing board catalog numbers.
Table 2 - Voltage Sensing Board Catalog Number
Sizing the Enclosure
Use the data in
to assist in calculating the enclosure size.
Table 3 - PowerBrick Specifications
Catalog Number
Voltage Sensing Board Input (3 phase, 50/60 Hz)
7703E-VSM
10,000…12,000V
7703E-VSN
12,001…14,400V
ATTENTION: The enclosure for the power stack assemblies must be adequately
sized to provide sufficient airflow to cool the units. Failure to provide adequate
cooling may result in reduced duty cycles or component failure.
Description
160 A, 340 A
Input Voltages
(50/60 Hz)
10,000…12,000V
12,001…14,400V
3 phase, +10%, -15%
Ambient Temperature
0 °C…40 °C (32 °F…104 °F)
Power Section
(for 3 phases)
30 SCR at 10…12 kV
36 SCR at 12.1…14.4 kV
Repetitive Peak Inverse
Voltage Rating
10 to12 kV…32,500 PIV
12.1…14.4 kV…39,000 PIV
Thermal Capacity
(1)
600% of FLA, 10 seconds
450% of FLA, 30 seconds
dv/dt Protection
R.C. Snubber Network
Maximum Heat
Dissipation (kW)
Start or Stop Cycle (at 450% FLA)
160 A
340 A
580 A
Continuous
(2)
10,000…12,000V
27
57
98
0.5
12,001…14,400V
32
69
117
0.5
Altitude
0…1000 m (0…3,300 ft)
(See Controller Deratings Table on page 6, Publication
1503-BR010F-EN-P
)
Net Shipping Weight
(3 phases)
Rating (kV)
10…12
12.1…14.4
Weight
kg (lbs)
570 (1260)
684 (1512)
(1) It may be possible to offer extended start times at reduced current or ambient temperature. Please consult Rockwell Automation factory for assistance.
(2) After bypass contactor/breaker is closed.