Set Point 9: Power Factor Trip Time Delay

Allowable Range: 0...100 s (0.01 second units)

Factory Default Setting: 50 s (0.5 second delay)

Set Point 10: Diagnostic Fault Mask

The Fault Mask value can be calculated by selecting either a Fault Mask groups or
individual faults. When switching between mask groups it is recommended that
the fault code be cleared/reset by selecting “Enable All Faults”.

Figure 22 - Diagnostic Fault Mask

Either group or individual mask can be used at one time. The resultant fault mask
code will be function of the 16 bit fault mask word use. It is possible to selectively
mask individual faults by adding up the fault values and entering the result. For
example, to disable the Reversed PF at Syncpro II and No Signal at Syncpro II,
the mask value would be 528 (16 +512). Refer to

Table 4 on page 49

for

additional information.

Figure 23 - Mask Individual Faults