Chapter 5

Programming SyncPro II

Set Point 2: Operating Frequency

This set point determines the operating system frequency. This allows the
SyncPro II to properly determine the appropriate minimum percent slip
frequency.

Figure 17 - Function Number

Set Point 3: Function Number

The function number entry determines the slope of the curve between the 50%
speed trip time and the 95% speed trip time – set point 4 and 5. Although the trip
time is set as 50% and 95% speed, the intermediate points between these values
can be shaped to cause the trips for 51% and 94% to occur more or less quickly
depending on which function number is selected. According to

Figure 17

, more

time is allowed when function 1 is selected, and less time is allowed when
function 5 is selected.