Main menu, Syncpro ii status, Main menu syncpro ii status – Rockwell Automation 1902 Syncpro II User Manual
Page 38
40
Rockwell Automation Publication 1902-IN001B-EN-E - April 2013
Chapter 5
Programming SyncPro II
Main Menu
The main menu provides access to the following screens.
SyncPro II Status
These screens are displayed when the motor is idle, starting, or running. The
PVc C400 automatically switches to one of the following screens after a period of
inactivity.
Figure 13 - Ready Mode
Ready
mode (
) indicates the SyncPro II has not detected any software or
hardware faults and is ready to start.
Figure 14 - Starting Mode
During the
Starting mode (
), the motor slip frequency in Hz power factor in %,
and time to a squirrel cage protection in seconds are displayed. The power factor value is
accompanied by either a < or >
symbol to indicate lagging or leading power factor. Typical
power factor readings during staring are lagging. If leading power factor is displayed, please
confirm voltage and current input connections for proper sequencing (e.g. V
ab
, I
c
).
SyncPro II Status
Provides idle, starting, running status information
View Set Points
Allows viewing of SyncPro II operation and protection set points.
Edit Set Points
Allows viewing of SyncPro II operation and protection set points
Alarm History
Lists alarm/fault history recorded with relative time stamping
Access Code
Allows users to log in or log out to provide access control to operation and protection set points.
Settings
Allow editing of general HMI configuration such as language, relative time/date stamp