Specifications, General, For phase angle transducer – Rockwell Automation 1902 Syncpro II User Manual
Page 17: Pvc c400 specifications, Micrologix 1500 specifications, General for phase angle transducer
Rockwell Automation Publication 1902-IN001B-EN-E - April 2013
17
Product Description
Chapter 1
Specifications
General
For Phase Angle Transducer
PVc C400 Specifications
See Publication
MicroLogix 1500
Specifications
See Publication
Operating Power
Input Line Voltage
120V AC, 50/60 Hz
Input Current
0...5 A
Temperature and Humidity
Temperature
(Maximum Ambient)
Operating: 0...40ºC (32...104ºF)
Storage: -20...65ºC (-4...149ºF)
Humidity
5...95% (non-condensing)
Maximum temperature: 40 ºC (104 ºF)
General
Accuracy
3% span
Housing
Flame retardant plastic case
Weight
2.4 kg maximum
Climate
Storage
-20...70 ºC (-4...158 ºF)
Temperature range
Operational at 0...60 ºC (32...140 ºF)
Calibrated at 23 ºC (73 ºF)
Humidity
Up to 95% relative humidity, non-condensing
Input
Frequency
50/60 Hz
Current
0.2...10 A
Range (A)
20...120%
Burden
5 VA maximum
Voltage
115...230V, ±10%
Range (V)
±20% (20...120% with separate auxiliary)
Burden 1 VA maximum
Overload Capacity
Six times rated current for 30 s
1.25 rated voltage for 10 s
Electrical Tests
Dielectric Test
2 kV RMS per BS 5458
Impulse Test
5 kV transient as BEAMA 219 and BS 923
Surge Withstand
ANSI C37-90A
Certification
CSA Approved