Specifications
10 Input/10 Output Card-Cat. Nos. 1799-ZCIOB, -D10U10BZC, -ZCIOV, & -D10U10VZC
Input Specification
Max
Min
Inputs per Block
10 sinking or sourcing, Type 1 + compatible
Off-state: Voltage
Current
5V dc
1.5 mA
-
-
On-state: Voltage
Current
30V dc
6 mA
10V dc
2 mA
Output Specification
Maximum
Minimum
Outputs per Block
10 sinking or sourcing, 0.5A, short circuit protected, pilot duty
Output Auxiliary Voltage
30V
10V
On-state Voltage Drop
250 mV
-
On-state Current
0.5 A
-
Off-state Leakage
20
µ
A
-
Card Current
(All Outputs On)
4.0 A
-
Surge Current - for 10 ms,
Repeatable Every 2 s
(Individual Outputs)
1.0 A
-
General Specifications
LED Indicators
Card Status - red/green, Network Status - red/green, Auxiliary
Power - green, DeviceLogix Status - green,
Input Point LED - yellow, Output Point LED -yellow
Dimensions - Millimeters
(Inches)
26H x 51W x 163D
(1.0H x 2.0W x 6.4D)
Operating Temperature
IEC 60068-2-1 (Test Ad, Operating Cold),
IEC 60068-2-2 (Test Bd, Operating Dry Heat),
IEC 60068-2-14 (Test Nb, Operating Thermal Shock):
-10...60
o
C (14...140
o
F)