Configure the parameters – Rockwell Automation 1799-D10U10VZC Zone Control I/O Cards User Manual
Page 14
14 Zone Control I/O Cards
Publication 1799-IN007D-EN-P - October 2005
Cyclic — the card produces and consumes its I/O cyclically at the rate configured by the
master on the DeviceNet network.
Polled — the master initiates communication by sending its polled I/O message to the card.
The card consumes the message, updates any outputs, and produces a response containing
the input data.
Change-of-state — a production occurs when an input changes. A heartbeat production
occurs if no input condition change occurs within the expected packet rate. This heartbeat
production tells the master that the card is ready to communicate. Consumption occurs when
data changes and the master produces new output data to the card.
Refer to the following table for the word and bit definitions:
Configure the Parameters
The Zone Control cards have 42 parameters that are configurable through a DeviceNet
configuration tool such as RSNetWorx for DeviceNet software. The DeviceNet
configuration tools require an Electronic Data Sheet (EDS) for the Zone Control cards to
configure the card’s parameters. Find the EDS file can be found at http://www.odva.org.
Byte
Bit 7
Bit 6
Bit 5
Bit 4
Bit 3
Bit 2
Bit 1
Bit 0
Prod 0 Input 7
Input 6
Input 5
Input 4
Input 3
Input 2
Input 1
Input 0
Prod 1 RSVD
Logic Ena
RSVD
Input 9
Input 8
Prod 2 Output 7 Output 6
Output 5 Output 4 Output 3 Output 2 Output 1 Output 0
Prod 3
RSVD
Output 9 Output 8
Prod 4 NetOut 7 NetOut 6 NetOut 5 NetOut 4 NetOut 3 NetOut 2 NetOut 1 NetOut 0
Prod 5 CCV 7
CCV 6
CCV 5
CCV 4
CCV 3
CCV 2
CCV 1
CCV 0
Prod 6 CCV 15
CCV 14
CCV 13
CCV 12
CCV 11
CCV 10
CCV 9
CCV 8
Cons 0 Output 7 Output 6
Output 5 Output 4 Output 3 Output 2 Output 1 Output 0
Cons 1
RSVD
Output 9 Output 8
RSVD = Reserved, Logic Ena = DeviceLogix enabled, NetOut = Network Output,
CCV = Configuration Consistency Value,