beautypg.com

0 programming, 1 analog rail module in automate systems – Rockwell Automation 61C350 2-In/2-Out 0-10 Volt Analog Rail Module User Manual

Page 23

background image

4Ć1

4.0 PROGRAMMING

This section describes how the data is organized in the module and

provides examples of how the module is accessed by application

programs.
When creating application programs, the programmer should

estimate the magnitude of input signals and output data because

both must be in the specified range of the Analog Rail module

(0Ć10V). Input signals greater than 10V will be clamped at 4095.

Input signals greater than approximately 11.3V will also cause the

overĆrange bit (12 decimal; 14 octal) to be set to 1. Signals less than

0V are clamped at zero (0). Signals less than approximately -1V will

also cause the underĆrange bit (13 decimal; 15 octal) to be set to 1.

See figure 4.1.

Counts

4095

0

<-1 = underĆrange

>11.3V = overĆrange

Volts

1 2 3 4 5 6 7 8 9 10

Ć1

11

Figure 4.1 Ć Input Signal Conversion

Recall that at a digital output = 4096, the output rolls over to zero

again. The programmer must include limits in the application

software to ensure that the data sent to output channels is always in

the specified range (allowable range = 0 to 4095).

4.1

Analog Rail Module in AutoMate Systems

This section describes how the Analog Rail is used with AutoMate

systems. Local Head mode allows all four channels on the module

to be updated at the end of the scan (normal I/O update rate in this

configuration), or during the scan using AIN and AOUT blocks (see

section 4.1.4). Rail mode allows only one channel to be updated at

the end of the scan (normal I/O update rate in this configuration), or

all four channels to be updated during the scan if AIN and AOUT

blocks are used.