3Ć4

Channel

Terminal

Number

Terminal Label

Signal

0

1

2

3

VĆOUT

Common

(no label)

0Ć10V+ output

common

(shield; no connection)*

1

4

5

6

VĆOUT

Common

(no label)

0Ć10V+ output

common

(shield; no connection)*

2

7

8

9

VĆIN

Common

(no label)

0Ć10V+ input

common

(shield; no connection)*

3

10

11

12

VĆIN

Common

(no label)

0Ć10V+ input

common

(shield; no connection)*

*This pin makes no electrical connection to the Analog Rail printed circuit board.

Step 10. For the two output channels, connect a shield wire from

the external hardware to the third terminal (terminals 3

and 6, respectively). Insert a jumper between terminals 2

and 3, and between 5 and 6. The shield wire at the

external hardware end of the cable should be cut short

and taped back to prevent any electrical contact. See

figure 3.2.

Step 11. For the two input channels, connect a shield wire from the

external hardware to the third terminal (terminals 9 and

12, respectively). The shield wire at the external hardware

end of the cable should be connected to the source

reference point. See figure 3.2.