3Ć8

For DCS 5000, AutoMax, or Distributed Power DĆC Drive

systems, use the DCS 5000 or AutoMax Programming

Executive software I/O Monitor function, respectively. Test

output channels by writinga value between 0 and 4095 to

those channels and usinga voltmeter to verify that the

signal on the terminal points (0 to 10V) is proportional. To

test input channels, verify that the input signal in the

channel (0 to 10V) is proportional to a voltmeter reading

at the terminal points.