beautypg.com

3 module replacement – Rockwell Automation 61C350 2-In/2-Out 0-10 Volt Analog Rail Module User Manual

Page 20

background image

3Ć6

WARNING

BE CAREFUL WHEN WRITING TO THE OUTPUTS TO INSURE THAT NO

UNEXPECTED MACHINE MOTION WILL RESULT. FAILURE TO OBSERVE THIS

PRECAUTION COULD RESULT IN BODILY INJURY OR DAMAGE TO EQUIPMENT.

For AutoMate systems, you must configure the AutoMate

processor using the AutoMate Programming Executive

(APX) before testing. See section 4.0 for more

information. After configuring the module, use the APX

Point Monitor function to test the module. You can test the

Analog Rail module's output channels by writing a value

between 0 and 4095 to those channels and, with a

voltmeter, verifying that the output on the terminal points

(0 to 10V) is proportional. To test input channels, verify

that the input signal in the channel (0 to 10V) is

proportional to a voltmeter reading at the terminal points.
For DCS 5000, AutoMax, or Distributed Power DĆC Drive

systems, use the DCS 5000 or AutoMax Programming

Executive software I/O Monitor function, respectively. Test

output channels by writing a value between 0 and 4095 to

those channels and using a voltmeter to verify that the

signal on the terminal points (0 to 10V) is proportional. To

test input channels, verify that the input signal in the

channel (0 to 10V) is proportional to a voltmeter reading

at the terminal points.

3.3

Module Replacement

Use the following procedure to replace the module.
Step 1.

Stop any application programs that are running.

Step 2.

Turn off power to the external hardware connected to the

input and output channels on the faceplate of the

module.

Step 3.

Turn off power to the Analog Rail module (120 VAC or

24 VDC).

Step 4.

Turn off power to the Reliance device connected to the

Analog Rail module.

Step 5.

Disconnect the I/O Rail cable from the Analog Rail

module.

Step 6.

Without disconnecting the wiring, remove the 12Ćpoint

terminal from the faceplate and set aside.

Step 7.

Without disconnecting the wiring, remove the 4Ćpoint

terminal from the faceplate and set aside. Disconnect the

ground wire from the bottom rightĆhand flange.

Step 8.

Loosen the screws that hold the Analog Rail module to

the panel and remove the module.

Step 9.

If the power supply you are using is 24 VDC, you need to

replace the factoryĆinstalled .25A fuse in the new module

with the .75A fuse that came in the shipping box with the

module. Use a screwdriver to release the fuse holder

located on the Analog Rail module faceplate. Pull the fuse