Rockwell Automation 1738-8CFGDLXM23 ArmorPoint Module with Configurable 24V DC Points and DeviceLogix User Manual
Page 17

ArmorPoint I/O Modules with 8 Configurable 24V DC Points and DeviceLogix 17
Publication
1738-IN027B-EN-E - February 2010
Network status
Off
Device is not online:
- Device has not completed dup_MAC-id test.
- Device not powered – check module status
indicator.
Green
Device is online and has one or more I/O
connections in established state.
Flashing green
Device is online but has no connections in
established state.
Flashing red
One or more I/O connections in timed-out state.
Red
Critical link failure – failed communication
device. Device detected error that prevents it
from communicating on the network.
Flashing red/green
Communication faulted device – the device has
detected a network access error and is in
communication faulted state.
Device has received and accepted an Identity
Communication Faulted Request – long
protocol message.
I/O status
Off
I/O is inactive.
Yellow
I/O is active and under control.
Flashing yellow
I/O is in charging state.
1738-8CFGDLXM8, 1738-8CFGDLXM12, 1738-8CFGDLXM23 Indicator Status
Status
Description