Rockwell Automation 1738-8CFGDLXM23 ArmorPoint Module with Configurable 24V DC Points and DeviceLogix User Manual
Page 15
![background image](/manuals/579962/15/background.png)
ArmorPoint I/O Modules with 8 Configurable 24V DC Points and DeviceLogix 15
Publication
1738-IN027B-EN-E - February 2010
Configuration of the 1734-8CFGDLX module must be done through
RSNetWorx for DeviceNet.
Data [46]
Peer 7 – EPR (ms)
Data [47]
Where:
Filter = 0...65535
μs (1000 = default)
FltM = Fault Mode (0 = Fault Value (default), 1 = Hold Last State)
FltV = Fault Value (0 = OFF (default), 1 = ON
IdIM = Idle Mode (0 = Idle Value (default), 1 = Hold Last State)
IdIV = Idle Value (0 = OFF (default), 1 = ON)
RACK = Produce with Rack Assembly 4 and Consume Rack Assembly 34
(0 = Disabled (default), 1 = Enabled)
CFO = DeviceLogix Communication Fault Override of Outputs
1 = Enabled. When enabled, the DeviceLogix program will continue to control the
outputs even in the event of a communication fault.
0 = Disabled (default). When disabled, the outputs will follow the Fault and Idle
settings.
DM = Dependent Mode
MP = Masterless Produce
0 = Disabled (default), 1 - Enabled. When enabled, the module will begin
producing data at powerup and after a connection with a controller is
terminated.
EPR = Expected Packet Rate in milliseconds
PIT = Production Inhibit Time in milliseconds
Slot / MacID = Address of peer
Data Map - Configuration Assembly 123