Communicate with your armorblock maxum module – Rockwell Automation 1792D-16BVT0CD ArmorBlock MaXum 16 Input Module with Complete Diagnostics User Manual
Page 10
10 ArmorBlock MaXum 16 Input Module with Complete Diagnostics
Publication 1792D-IN053A-EN-P - August 2002
•
1792D-IN009 ArmorBlock MaXum Cable Base Installation Guide
•
DN-6.7.2 DeviceNet Cable Planning and Installation Manual
Communicate With Your ArmorBlock MaXum Module
This ArmorBlock module’s I/O is exchanged with the master through
a polled, change-of-state, or cyclic connection.
The module consumes and produces input data as follows:
Cyclic - allows configuration of the block as an I/O client. The block
will produce its I/O cyclically at the rate configured.
Polled - a master initiates communication by sending its polled I/O
message to the module. The 16 input module scans the inputs and
fault bits producing a response that reflects their status.
Change of State - productions occur when an input changes or a
fault condition occurs. If no input or fault condition change occurs
within the expected packet rate, a heartbeat production occurs. This
heartbeat production tells the scanner module that the module is alive
and ready to communicate.
Refer to the table below for the word/bit definitions.
Note: If you are using DeviceLogix, please refer to publication no.
1792-TD001 for the alternate I/O assemblies for DeviceLogix.
Type of I/O Connections
Consumes
Produces
Cyclic
0 Byte
6 Bytes
Polled
0 Byte
6 Bytes
Change-of-State
0 Byte
6 Bytes
Bit
07
06
05
04
03
02
01
00
Produced 0
In 7
In 6
In 5
In 4
In 3
In 2
In 1
In 0
Produced 1
In 15
In 14
In 13
In 12
In 11
In 10
In 9
In 8
Produced 2
ISC-7
ISC-6
ISC-5
ISC-4
ISC-3
ISC-2
ISC-1
ISC-0
Produced 3
ISC-15
ISC-14
ISC-13
ISC-12
ISC-11
ISC-10
ISC-9
ISC-8
Produced 4
OW-7
OW-6
OW-5
OW-4
OW-3
OW-2
OW-1
OW-0
Produced 5
OW-15
OW-14
OW-13
OW-12
OW-11
OW-10
OW-9
OW-8
Where: I = Input ISC = Input Short Circuit in Sensor Source Voltage OW = Off Wire