Dip switch 2 settings, Rack size (sw2-5 and sw2-6), Last rack (sw2-4) – Rockwell Automation 1747-DCM,D17476.8 Direct Communication Module User Manual
Page 36

Chapter 4
Module Configuration
4–6
Rack Size (SW2-5 and SW2-6)
The logical rack size allocates image space in the scanner for each DCMs I/O
data. The DCM allows 1/4, 1/2, 3/4, and full rack addressing. SW2 switches
5 and 6 define the rack size.
Rack Size
SW2-5
SW2-6
1/4 Logical Rack
ON
ON
1/2 Logical Rack
ON
OFF
3/4 Logical Rack
OFF
ON
Full Logical Rack
OFF
OFF
Important: The DCM image cannot cross logical rack boundaries.
Therefore, as an example, configuring the module for 1/2
logical rack with starting group 6 will cause a configuration
error. Refer to Starting I/O Group Number on page 4–2.
Last Rack (SW2-4)
Switch 4 of SW2 must be set to the OFF position if the DCM shares its
logical rack with at least one other adapter and has been assigned the highest
I/O group number in that logical rack.
Last Rack
SW2-4
Yes
OFF
No
ON
Remote I/O Scanner
SLC Output Image (to the PLC)
Module 2 Configured As:
Logical Rack Address 1
I/O Group 2
Module Rack Size 1/4
Module 1 Configured As:
Logical Rack Address 1
I/O Group 0
Module Rack Size 1/4
Module 3 Configured As:
Logical Rack Address 1
I/O Group 4
Module Rack Size 1/4
Module 4 Configured As:
Logical Rack Address 1
I/O Group 6
Module Rack Size 1/4
Direct Communications Module 1
Octal
15 14 13 12 11 10 7
6
5
4
3
2
1
0
Group 0, Word 0
Group 1, Word 1
Group 2, Word 2
Group 3, Word 3
Group 4, Word 4
Group 5, Word 5
Group 6, Word 6
Group 7, Word 7
17 16
Module 1
Module 2
Module 3
Module 4
Module 4 is the last device in the logical rack.
Because Module 4 is the last RIO adapter
in a logical rack shared by other adapter(s),
SW2 switch 4 must be in the OFF position.
Logical
Rack 1
13 12 11 10
9
8
7
6
5
4
3
2
1
0
15 14
Decimal
Bit Number:
DIP Switch 2 Settings