5-2 Status Indicators and Troubleshooting
Publication 1756-UM524B-EN-P - December 2008
Use the LED Status Indicators
The 1756-CLX/C module has the following LED status indicators. Use these indicators to
troubleshoot module status.:
Table 5.A LED Status Indicators
This LED
When
Means
So you should
BAT (RED)
ON
The battery is low.
Replace the module.
The battery is charging. The BAT
LED turns OFF within a few
minutes after power is applied.
Wait for the battery to finish
charging.
OFF
The Battery is charged.
The module is not powered up.
Do nothing. The module is ready
for use.
Apply power to the module.
USR
(GREEN)
ON/OFF
Data is being sent or received
over the NeXUS port.
Do nothing. The module is
operating correctly.
OFF
No data is being sent or received
over the NeXUS port.
The module is not powered up.
Check the Communication port
LEDs. If:
• LEDs are working properly,
restart the module
• LEDs are not working
properly, follow the
instructions in Table 5.B on
page 5-3
• the problem persists, replace
the module
Apply power to the module.
OK
(STATUS)
GREEN
The module is operating
correctly.
Do nothing. The module is ready
for use.
RED
The module has experienced an
error.
Restart the module. If the
problem persists, replace the
module.
OFF
The module is not powered up.
Apply power to the module.