Environmental Specifications
Attribute
Value
Operational Temperature
IEC 60068-2-1 (Test Ad, Operating Cold),
IEC 60068-2-2 (Test Bd, Operating Dry Heat),
IEC 60068-2-14 (Test Nb, Operating Thermal Shock):
-20…55 °C (-4…131 °F)
Storage Temperature
IEC 60068-2-1 (Test Ab, Unpackaged Non-operating Cold)
IEC 60068-2-2 (Test Bb, Unpackaged Non-operating Dry Heat)
IEC 60068-2-14 (Test Na, Unpackaged Non-operating Thermal
Shock) -40…85 °C (-40…185 °F)
Relative Humidity
IEC 60068-2-30 (Test Db, Unpackaged Damp Heat):
5…95% noncondensing
Shock Operating
Nonoperating
IEC 60068-2-27 (Test Ea, Unpackaged Shock): 30 g
IEC 60068-2-27 (Test Ea, Unpackaged Shock): 50 g
Vibration
IEC 60068-2-6 (Test Fc, Operating): 5 g @ 10…500 Hz
Conducted RF Immunity
IEC 61000-4-6: 10V rms with 1 kHz sine-wave 80% AM from
150 kHz…80 MHz
EFT/B Immunity
IEC 61000-4-4: ±2 kV at 5 kHz on power ports
±2 kV at 5 kHz on signal ports
±1 kV at 5 kHz on communication ports
ESD Immunity
IEC 61000-4-2: 4 kV contact discharges
8 kV air discharges
Enclosure Type Rating
None (open-style)
Emissions
CISPR 11:
Group 1, Class A
Radiated RF Immunity
IEC 61000-4-3: 10V/m with 1 kHz sine-wave 80%AM from
30…2000 MHz
10V/m with 200 Hz 50% Pulse 100%AM at 900 MHz
1 V/m with 1 kHz sine-wave 80%AM from 2000…2700 MHz
Surge Transient
Immunity
IEC 61000-4-5:
±2 kV line-earth(CM) on power ports
±1 kV line-line(DM) and ±2 kV line-earth(CM) on signal ports
±2 kV line-earth(CM) on communication ports